| Q1 |
|
For the APS-7000 series, can the step time of Sequence or Simulation exceed 3600 seconds (1 hour)? |
For the APS-7000 series, single step time of Sequence or Simulation is 3600 seconds (1 hour).
If your application requires a sequence or a simulation step time of more than 1 hour, you can use the Jump function to achieve it.
| Q2 |
|
Precautions for testing HVDC server power supply (ODCC) or LVDC communication power supply? |
Mission Critical applications such as communication equipment rooms (such as 4G, 5G base stations) and data centers (IDC) will have a great impact due to power failure. Therefore, such constructions will have emergency power supplies such as UPS. In order to save energy, these data centers also desire to directly use regenerative energy or the DC voltage of the UPS to reduce the consumption of the conversion.
Therefore, in addition to AC input, the current power supply also supports 48V DC input LVDC and 180~400V DC input HVDC. When testing this type of power supply, the conventional AC power supply does not have the DC mode, so it is difficult to perform the test.
GW Instek ASR-2000 series and ASR-3000 series AC/DC power supplies are instruments developed for the above applications.
Precautions for purchasing AC and DC power supply:
2. Whether it can be seamlessly converted from AC output to DC output: Most AC/ DC power supplies turn off AC and then turn on DC, so there will be a power outage at the moment of conversion. GW Instek ASR-2000 and ASR-3000 are seamless transition designs.
| Q3 |
|
How do you eliminate the voltage drop caused by the wiring of the power supply? The application of output Remote Sense |
Connecting the power supply to the device under test (DUT or DUC) requires an additional test lead, and the resistance of the test lead will cause a slight voltage drop, so that the DUT cannot get the expected output voltage. In order to improve this problem, the power supply is designed with the function of Remote Sense. The remote sense function senses the actual voltage value received by the DUT through the additional wiring of S+ and S-.
Take the 3.3V output as an example, because the voltage drop of the wire, there is only 3.2V left on the circuit under test. Through the report of the remote sense, the power supply will increase the output until the voltage reported by the remote sense is 3.3V, this design can eliminate the voltage drop of the wire.
Precautions on using Remote Sense:
| Q4 |
|
How do you verify fuses and circuit breakers with the most appropriate cost? |
Test fuses and circuit breakers need transient current to test whether the operation is normal.
It is a design issue when it does not disconnect as the function
It is a quality issue when it does not connect as the function
GW Instek electronic loads with the Turbo mode can help users to verify these two issues at the most appropriate cost.
Turbo mode can provide double the rated current or power in a short time (1 second).
Electronic loads with the Turbo mode include:
AEL-5000系列GW Instek brand: The AEL-5000 series
3310G系列,3350G系列,3270系列,3282系列Prodigit brand: the 3310G series, the 3350G series, the 3270 series, the 3282 series
Other applications of Turbo mode: Short circuit of AC power supply, OCP, OPP test
| Q5 |
|
Decrypt the zero voltage (0 Volts) start of the electronic load |
The basic element of an electronic load is a MOSFET, which is a voltage-controlled variable resistor.
The electronic load is an important device for testing the transient response of the power supply. If we simplify the electronic load as a MOSFET, when the MOSFET is connected to the power supply, the voltage of the power supply must reach the MOSFET Vds voltage before current flows through it. . Therefore, the electronic load cannot be started at zero voltage from its basic structure.
How do you accomplish a zero voltage startup application?
You only need to connect a power supply in series to offset the voltage change of Vds to start at zero voltage.
Possible applications: supercapacitors, fuel cells
| Q6 |
|
Can PEL-3211 booster be connected in parallel with PEL-3021(175W) or PEL-3041(350W)? |
PEL-3211 booster can only be connected in parallel with PEL-3111.
Five PEL-3111 units can be connected in parallel or PEL-3111 can be combined with PEL-3211*4
A maximum of five electronic loads of the same type as PEL-3021 or PEL-3041 can be connected in parallel.
Five PEL-3021 units can be connected in parallel
Five PEL-3041 units can be connected in parallel
The same is true for H series high pressure models
Application keyword: parallel connection of electronic loads
| Q7 |
|
Does the DC mode of the AC power supply have the constant current (CC) output of the DC power supply? |
The DC mode of the AC power supply does not have the constant current (CC) output of the DC power supply.
The DC mode of the AC power supply can only provide a constant voltage (CV) output. When the DC power supply is overloaded, it will become a constant current (CC) output. When the DC mode of the AC power supply is overloaded, the output will stop.
| Q8 |
|
The output mode of the DC power supply, constant voltage mode (CV mode) and constant current mode (CC mode) |
The output of most DC power supplies is to provide a set voltage, which we call the constant voltage mode (CV mode). It is better to use "set fixed output voltage" to describe the overall meaning. At this time, the current of the power supply varies with load change.
However, this fluctuating current cannot exceed the maximum design current of the power supply (to meet the application and price design goals) or the maximum set current (to protect the circuit under test), so once the load current exceeds any of the above current values, the output of the power supply will switch from CV mode to constant current mode (CC mode)
Take the DC power with the maximum design voltage/current of 30V/3A as an example: when the load does not exceed 3A, the power supply is in constant voltage mode, and the set output voltage can be 0~30V (according to the minimum set resolution). Taking 12V as an example, as long as the load does not exceed 3A, the ideal output voltage is a fixed 12V (the unideal value is affected by the output accuracy, ripple/noise, linear regulation, load regulation), and the current value varies with load change.
Once the load exceeds 3A (according to Ohm's law 12V/3A=4 ohms, when it is lower than 4 ohms, the load will exceed 3A), since the power supply can only provide 3A, it will be converted to constant current mode at this time, the current is 3A, the output voltage varies with load change.
The relationship between load, current and resistance is as follows: Generally, the reason why the current does not reach the set current is that the resistance is not small enough.
Large load = large current = small resistance; small load = small current = large resistance
How to set the maximum current:
Knob-type setting: The output must be short-circuited to see the current reading. It is recommended to turn the knob to the state where the current is 0. If the knob is at the maximum current position, there may be sparks when the output is short-circuited (possibly frightened). Slowly turn the knob from the position where the current reading value is 0 to the desired maximum setting current.
Key-press setting: Just use the numerical and unit keys to input the required maximum setting current.
Application keywords: constant current output, constant current output
| Q9 |
|
Keithley 2400 is a widely used Source Measure Unit in the market. Does GSM-20H10 provide compatible commands? |
The launch of GSM-20H10 is to provide users with a more economical choice on the entry-level Source Measure Unit.
Therefore, we also take into account users’ requirements to replace the instrument. Therefore, all the commands on Keithley 2400 can be recognized and executes by GSM-20H10.
But there are two special cases users must consider:
| Q10 |
|
The CH3 overload indicator turned on is this error? |
When the output Current level exceeds 3A, the overload indicator turns red and CH3 operation mode switches from Constant Voltage to Constant Current. Note:"overload"in this case does not mean an abnormal operation please remove your load then overload indicator would be turns off if you have higher voltage and current requirement you can shift to CH1 or CH2 for operating.
| Q11 |
|
What is the key lock function of the GPD-3303S / GPD-3303D? |
The LOCK key to lock the front panel key operation. When the LOCK key function enable that the LED turns on. To unlock, press the LOCK key for 2~3 seconds then the key LED will be turn off.
| Q12 |
|
The load wire does not fit into the terminal. |
Make sure you are NOT connecting the load wire to the remote sensing terminal. Please Refer our user manual page30 for connection details.